The offline monitor of the IR420-D6 series is designed to monitor the insulation resistance of loads in the de-energized state. These loads, usually temporarily operated or de-energized most of the time, e.g. fire extinguisher pumps, slide valve drives etc are supplied from solidly grounded or ungrounded systems. During the shut-down periods, however, humidity or other effects may cause insulation faults in the wiring or the loads which may go undetected. Switching the device on may then lead to the tripping of the protective device or may even result in motor fires and the device cannot be operated. In combination with a coupling device, the Isometers can also be used for higher voltages.
The offline monitor of the IR420-D6 series is designed to monitor the insulation resistance of loads in the de-energized state. These loads, usually temporarily operated or de-energized most of the time, e.g. fire extinguisher pumps, slide valve drives etc are supplied from solidly grounded or ungrounded systems. During the shut-down periods, however, humidity or other effects may cause insulation faults in the wiring or the loads which may go undetected. Switching the device on may then lead to the tripping of the protective device or may even result in motor fires and the device cannot be operated. In combination with a coupling device, the Isometers can also be used for higher voltages.
Type | Supply voltage* US | Response value Ran | System leakage capacitance Ce | Art. No.** |
---|---|---|---|---|
IR420-D6-1 | DC 9,6…94 V / AC 16…72 V, 42…460 Hz | 100 kΩ…10 MΩ | ≤ 10 µF | B71016415 B91016415 |
IR420-D6-2 | DC 70…300 V / AC 70…300 V, 42…460 Hz | 100 kΩ…10 MΩ | ≤ 10 µF | B71016407 B91016407 |
* Absolute values
**(B7… = push-wire terminal / B9… = screw-type terminal)
Type | Nominal system voltage* Un | Art. No. |
---|---|---|
AGH520S | AC 0…7200 V, 50…400 Hz | B913033 |
Mounting clip for screw mounting (1 piece per device) | B98060008 | |
Mounting frame XM420 | B990994 |
Name | Category | Size | Language | Timestamp | D-/B-Number |
---|---|---|---|---|---|
UKCA - IR42x | Declarations of Conformity | 140.6 KB | 2022/12/2020.12.2022 | ||
IR42x | CE Declarations of Conformity | 94.2 KB | 2022/08/1212.08.2022 | ||
IR420-D6 | Manuals | 1.3 MB | EN | 2021/05/0707.05.2021 | D00117 |
IR420-D6 | Datasheets | 542.3 KB | EN | 2024/07/3030.07.2024 | D00117 |
XM420 interface options | Datasheets | 223.5 KB | EN | 2019/05/1313.05.2019 | D00051 |
Changed variants of relays from goldplated to silver-plated contacts | Technical Information | 166.3 KB | EN | 2022/06/2727.06.2022 |