ISOMETER® isoPV1685 Series

  • Application photovoltaic systems up to AC 1000 V/DC 1500 V
  • Separately adjustable response values 200 Ω…1 MΩ
  • Automatic adaptation to the system leakage capacitance
    up to 2000 μF
  • Interface selectable RS-485 or Modbus

The device is used for insulation and residual current monitoring of large photovoltaic systems up to 1500 V designed as IT systems. The measurement method specially developed for slow voltage fluctuations (MPP-Tracking) monitors the insulation resistance even in systems equipped with large solar generator panels where extremely high system leakage capacitances against ground exist due to interference suppression methods. Adaptation to system-related high leakage capacitances also occurs automatically. The device generates locating current pulses required for ground-fault location. That allows the localization of the ground fault using permanently installed or mobile ground-fault locators. Integrated ground-fault monitoring allows fast signalling of a measured ground faults on the AC side (inverter, transformer).

Questions? Contact us!

ISOMETER® isoPV1685/isoPV1685PFR
ISOMETER® isoPV1685/isoPV1685PFR
  • Application photovoltaic systems up to AC 1000 V/DC 1500 V
  • Separately adjustable response values 200 Ω…1 MΩ
  • Automatic adaptation to the system leakage capacitance
    up to 2000 μF
  • Interface selectable RS-485 or Modbus

The device is used for insulation and residual current monitoring of large photovoltaic systems up to 1500 V designed as IT systems. The measurement method specially developed for slow voltage fluctuations (MPP-Tracking) monitors the insulation resistance even in systems equipped with large solar generator panels where extremely high system leakage capacitances against ground exist due to interference suppression methods. Adaptation to system-related high leakage capacitances also occurs automatically. The device generates locating current pulses required for ground-fault location. That allows the localization of the ground fault using permanently installed or mobile ground-fault locators. Integrated ground-fault monitoring allows fast signalling of a measured ground faults on the AC side (inverter, transformer).

Questions? Contact us!

Features

Only device version isoPV1685P provide a locating current injector.

  • Insulation monitoring of large-scale photovoltaic systems
  • Measurement of low-resistance insulation faults
  • Separately adjustable response values Ran1 (alarm 1) and Ran2 (alarm 2) (both 200 Ω…1 MΩ) for prewarning and alarm. Ran1Ran2 applies.
  • Automatic adjustment to high system leakage capacitances up to 2000 μF, selectable range
  • Connection monitoring of L+, L- for reverse polarity (DC only)
  • Integrated locating current injector up to 50 mA (isoPV1685P only)
  • Device self test with automatic message in the event of a fault
  • Alarm relays separately adjustable for insulation fault 1, insulation fault 2
  • CAN interface to output measured values, statuses and alarms
  • RS-485 interface
    – isoPV1685P: BMS bus, e.g. to control the insulation fault location
    – isoPV1685RTU: BMS bus or Modbus (can be switched using the DIP switch)
  • μSD card with data logger and history memory for alarms

Applications

  • Large PV systems designed as IT systems up to AC 1000 V/DC 1500 V

ISOMETER® isoPV1685 Series Variant(s)

TypeResponse value rangeSupply voltage UsNominal system voltage UnArt. No.
isoPV1685RTU-425200 Ω…1 MΩDC 18…30 VAC 0…1000 V/DC 0…1500 VB91065603
isoPV1685P-425200 Ω…1 MΩDC 18…30 VDC 0…1500 VB91065604

Downloads for ISOMETER® isoPV1685 Series

NameCategorySizeLanguageTimestampD-/B-Number
UKCA - isoXX1685 Declarations of Conformity 122.0 KB 2023/06/1212.06.2023
isoPV1685RTU - Modbuseinstellungen Application Notes 252.9 KB DE2023/07/0606.07.2023D00007
isoPV1685RTU - Modbus settings Application Notes 250.2 KB EN2023/07/0606.07.2023
isoPV1685P Datasheets 2.0 MB DE2024/09/0505.09.2024D00007
isoPV1685P Datasheets 2.0 MB EN2024/09/0505.09.2024D00007
isoPV1685P Manuals 4.9 MB DE2024/09/0303.09.2024D00007
isoPV1685P Manuals 4.8 MB EN2024/09/0505.09.2024D00007
Erneuerbare Energien: Photovoltaik Market Segment Brochures 2.0 MB DE2023/06/1616.06.2023
Renewable energies: Photovoltaics Market Segment Brochures 2.0 MB EN2023/06/1616.06.2023
CAN communication for isoPV1685 Manuals 367.2 KB EN2023/04/0505.04.2023D00007
isoXX1685 CE Declarations of Conformity 89.1 KB 2023/06/1212.06.2023
isoPV1685RTU/isoPV1685P Manuals 2.4 MB EN2023/04/0505.04.2023D00007
isoPV1685/isoPV1685PFR Appendix A Manuals 494.6 KB EN2019/05/1313.05.2019D00007
isoPV1685RTU/isoPV1685P Datasheets 645.5 KB EN2023/04/0505.04.2023D00007
isoPV1685RTU/isoPV1685P Quickstarts 1.0 MB EN2023/04/0505.04.2023D00007