The device is used for insulation and residual current monitoring of large photovoltaic systems up to 1500 V designed as IT systems. The measurement method specially developed for slow voltage fluctuations (MPP-Tracking) monitors the insulation resistance even in systems equipped with large solar generator panels where extremely high system leakage capacitances against ground exist due to interference suppression methods. Adaptation to system-related high leakage capacitances also occurs automatically. The device generates locating current pulses required for ground-fault location. That allows the localization of the ground fault using permanently installed or mobile ground-fault locators. Integrated ground-fault monitoring allows fast signalling of a measured ground faults on the AC side (inverter, transformer).
The device is used for insulation and residual current monitoring of large photovoltaic systems up to 1500 V designed as IT systems. The measurement method specially developed for slow voltage fluctuations (MPP-Tracking) monitors the insulation resistance even in systems equipped with large solar generator panels where extremely high system leakage capacitances against ground exist due to interference suppression methods. Adaptation to system-related high leakage capacitances also occurs automatically. The device generates locating current pulses required for ground-fault location. That allows the localization of the ground fault using permanently installed or mobile ground-fault locators. Integrated ground-fault monitoring allows fast signalling of a measured ground faults on the AC side (inverter, transformer).
Only device version isoPV1685P provide a locating current injector.
Type | Response value range | Supply voltage Us | Nominal system voltage Un | Art. No. |
---|---|---|---|---|
isoPV1685RTU-425 | 200 Ω…1 MΩ | DC 18…30 V | AC 0…1000 V/DC 0…1500 V | B91065603 |
isoPV1685P-425 | 200 Ω…1 MΩ | DC 18…30 V | DC 0…1500 V | B91065604 |
Name | Category | Size | Language | Timestamp | D-/B-Number |
---|---|---|---|---|---|
UKCA - isoXX1685 | Declarations of Conformity | 122.0 KB | 2023/06/1212.06.2023 | ||
isoPV1685RTU - Modbuseinstellungen | Application Notes | 252.9 KB | DE | 2023/07/0606.07.2023 | D00007 |
isoPV1685RTU - Modbus settings | Application Notes | 250.2 KB | EN | 2023/07/0606.07.2023 | |
isoPV1685P | Datasheets | 2.0 MB | DE | 2024/09/0505.09.2024 | D00007 |
isoPV1685P | Datasheets | 2.0 MB | EN | 2024/09/0505.09.2024 | D00007 |
isoPV1685P | Manuals | 4.9 MB | DE | 2024/09/0303.09.2024 | D00007 |
isoPV1685P | Manuals | 4.8 MB | EN | 2024/09/0505.09.2024 | D00007 |
Erneuerbare Energien: Photovoltaik | Market Segment Brochures | 2.0 MB | DE | 2023/06/1616.06.2023 | |
Renewable energies: Photovoltaics | Market Segment Brochures | 2.0 MB | EN | 2023/06/1616.06.2023 | |
CAN communication for isoPV1685 | Manuals | 367.2 KB | EN | 2023/04/0505.04.2023 | D00007 |
isoXX1685 | CE Declarations of Conformity | 89.1 KB | 2023/06/1212.06.2023 | ||
isoPV1685RTU/isoPV1685P | Manuals | 2.4 MB | EN | 2023/04/0505.04.2023 | D00007 |
isoPV1685/isoPV1685PFR Appendix A | Manuals | 494.6 KB | EN | 2019/05/1313.05.2019 | D00007 |
isoPV1685RTU/isoPV1685P | Datasheets | 645.5 KB | EN | 2023/04/0505.04.2023 | D00007 |
isoPV1685RTU/isoPV1685P | Quickstarts | 1.0 MB | EN | 2023/04/0505.04.2023 | D00007 |